Brand Name GENY
Model Number YC1893DI
Certification ISO 9001
Place of Origin China
Minimum Order Quantity 1 PCS
Price negotiation
Supply Ability 30 PCS per month
Delivery Time 30 days after order confirmed
Packaging Details Plywood case
Brand GENY
Model YC1893DI
Accuracy class 0.05, 0.1
Position 6, 12, 24, 48
phase Three phase
power electric

Description:

1)  Installing the ICT in each meter position to test three-phase close - link meter

2)  The meter test system can measure mechanical meter, electronic mechanical meters and electronic meter by ways of automatic, semi-automatic or manual operation.

3)  Meters under testing: 3P4W, 3P3W, 1P2W

4)  Testing mode: active power, reactive power, cross connected reactive power

5)  Simultaneously measure meters with same specifications but different meter constants

6)  Automatic positioning rotor mark of disc of mechanical meter, with more efficiency.

7)  Starting test and creeping test

8)  With the protection function of overload, short voltage circuit and open current circuit.

9)  The swing together of the scanning heads simplifies the control.

10)  Aluminum alloy material, light and strong and corrosion resistant

11)  The testing software with friendly Windows 2000 /XP /7 /8 /10 operation system, includes functional module of all kinds of modern energy meter needed, to reality error test, harmonic test, demand test, influence test etc,.
Specifications:

Test of closed I-P link meters with isolated current transformer(ICT)

Accuracy class : 0.05

Technical spec.

YC1893D-ICT-6

YC1893D-ICT-12

YC1893D-ICT-24

YC1893D-ICT-48

Number of meter positions equipped ICT

6

12

24

48

Accuracy class of ICT

0.05 / 0.01

Accuracy

0.05

Power Source

YCS-103-250

YCS-103-600

YCS-103-1200

YCS-103-2500

Standard Meter

SZ03A-K6 / SZ03A-K8 (customized)

Scanning Head

YCG-S Series

Voltage


Test voltage output(Phase-Neutral)

3x(24V~288V)(or customized)

Power of the voltage output

Max. 3x100VA

Max. 3x250VA

Max.

   3x500VA

Max.

   3x1000VA

Resolution

Better than 0.01% of full scale value of range

Setting accuracy

Better than 0.05% at the final range value

Stability

Better than 0.005% /h (integration time 150s)

Load regulation from 0~max. load

Better than 0.01%

Distortion factor

Better than 0.3% for linear resistance load

Harmonic

2nd~21stfree programmable

Current


Test current output

3x(1mA~100A)

Power of the current output

Max. 3x150VA

Max. 3x350VA

Max. 3x750VA

Max. 3x1500VA

Resolution

Better than 0.01% of full scale value of range

Setting accuracy

Better than 0.05% at the final range value

Stability

Better than 0.005% /h (integration time 150s)

Load regulation from 0~max. load

Better than 0.01%

Distortion factor

Better than 0.3% for linear resistance load

Harmonic

2nd~21stfree programmable

Phase angle


Range

0~360⁰

Resolution

0.01⁰

Setting accuracy

0.1⁰

Frequency


Range

45Hz~65Hz

Resolution

0.01Hz

Error display


Type of error display

Red LED

Resolution of error displays

8 digitals

Other


Voltage supply

3x220/380V±10%(or customized)
50/60Hz ±2Hz

Ambient temperature

-10°C~+40°C

Relative humidity

35%~85%

Applications:

Nation-level utility companies

Governmental bureaus of metrology

Big energy meter manufacturers

GENY After-Sale Service

For rapid and efficient after-sale service, please contact our After-Sale Service Department directly.

We are already to support you to answer your technical questions regarding of both hardware and software, such like debugging, trouble shooting and repairs.

Phone: +86 0208703-6713

(from 08:30 am to 17:00 pm GMT+8)

Fax: +86 0208703-7211

e-mail address: geny@geny.cn
Primary Competitive Advantages:

High quality product

Over 18 months long warranty

High accuracy class: 0.05

3~48 Three Phase Electric Energy Meter Test bench

Extremely high power stability

Timing error test

Influence test of voltage, frequency, and harmonic

Installing RS232, Ethernet communication port in each meter position.

Tilt impact test (optional)

Established in 1987, GENY is well-known as one of the leading and professional manufacturers and suppliers of full auto mode three phase electricity meter test systems for test / calibration of closed i-p link muts in max 24 positions in China. Please rest assured to buy the quality equipment made in China from us and experience our good after-sale service.